Troubleshooting
Extended Local I/O 5-42
791 0x0317 INVALID SCHEDULE DATA The ControlNet cable from the originating node to
the programming terminal was broken or
disconnected when the ControlNet network was
configured.
Fix and/or reconnect the ControlNet cable and
reconfigure the ControlNet network.
The originating node was not powered when the
ControlNet network was configured.
Supply power to the originating node and
reconfigure the ControlNet network.
797 0x31D INVALID TARGET TAG The PLC-5C is requesting data from a
ControlLogix tag that is not configured as a
producer.
Change the PLC-5C I/O map entry to use the
correct tag.
Reconfigure the tag in the ControlLogix processor
to be a producer.
798 0x31E TAG IS ALREADY PRODUCED THE
MAXIMUM NUMBER OF TIMES
The PLC-5C is requesting data from a
ControlLogix tag that is already being produced
the maximum number of times.
In the ControlLogix processor, increase the
number of times this tag can produce data.
65522 0xFFF2 CONFIGURATION FROM MAP ENTRY
FAILED
The ControlNet cable from the originating node to
the target node is broken or disconnected.
Fix and/or reconnect the ControlNet cable.
The target node is not powered. Supply power to the target node.
The target slot is empty. Insert the proper module in the correct slot of the
target node.
The target slot contains the wrong module type.
An incorrect module or slot was entered in the
map table.
Edit the I/O map table to show the correct module
type and slot.
65523 0xFFF3 CONTROLNET TRANSFER QUEUE FULL The immediate CIO instruction could not be
executed because the queue is full.
Edit the ladder program so that the number of
active 1771 READ/WRITE CIO instructions is equal
to or less than the maximum of 32.
Decimal Code Hex. Code Error Message Explanation/Possible Cause(s) Possible Corrective Action(s)
ControlNet Errors