User manual

Troubleshooting
Extended Local I/O 5-41
Troubleshooting
Extended Local I/O 5-41
772 0x0304 NO SCHEDULED CONFIGURATION The ControlNet cable from the originating node to
the keeper was broken or disconnected when the
ControlNet network was configured.
Fix and/or reconnect the ControlNet cable and
reconfigure the ControlNet network.
The keeper was not powered when the ControlNet
network was configured.
Supply power to the keeper and reconfigure the
ControlNet network.
The originating and/or target node is not properly
configured to send scheduled data.
Edit the I/O map table of the originating and/or
target nodes to send scheduled data.
773 0x0305 SCANNER SIGNATURE MISMATCH The ControlNet cable from the originating node to
the keeper was broken or disconnected when the
ControlNet network was configured.
Fix and/or reconnect the ControlNet cable.
Reconfigure the ControlNet network by enabling
and accepting edits with RSNetWorx.
The ControlNet processor was not configured on
the current network.
Reconfigure the ControlNet network by enabling
and accepting edits with RSNetWorx.
The ControlNet network was formed by joining
two existing ControlNet networks.
Reconfigure the new ControlNet network by
enabling and accepting edits with RSNetWorx.
774 0x0306 KEEPER NOT AVAILABLE The ControlNet cable from the originating node to
the keeper is broken or disconnected.
Fix and/or reconnect the ControlNet cable.
The keeper is not powered. Supply power to at least one ControlNet
processor.
No keeper exists on the ControlNet network. Add at least one ControlNet processor to the
network. Reconfigure the ControlNet network by
enabling and accepting edits with RSNetWorx.
789 0x0315 INVALID PATH SEGMENT TYPE The map table is corrupted. Reenter the I/O map entry that is failing.
The target node of the CIO instruction is not the
correct I/O adapter.
Edit the ladder program so that the correct target
node is used.
Replace the target node with the correct adapter.
Decimal Code Hex. Code Error Message Explanation/Possible Cause(s) Possible Corrective Action(s)
ControlNet Errors