User manual

Troubleshooting
Extended Local I/O 5-38
275 0x0113 OUT OF CONNECTIONS The maximum number of connections to/from this
node has been exceeded.
Reduce the number of I/O connections, MSG
instructions, or CIO instructions to/from this node.
276 0x0114 PRODUCT CODE MISMATCH The target node/module does not match the
node/module entered in the map table.
Replace the target node/module with the correct
node/module.
277 0x0115 PRODUCT TYPE MISMATCH Correct the I/O map table.
278 0x0116 REVISION MISMATCH The series/revision of the target node/module
does not match the series/revision entered in the
map table.
Replace the target node/module with the correct
node/module.
Correct the I/O map table.
279 0x0117 INVALID CONNECTION POINT The PLC-5C is requesting data from a
ControlLogix tag that does not exist.
Change the PLC-5C I/O map entry to use the
correct tag.
Change or add the tag to the ControlLogix
processor.
The PLC-5C does not support ControlNet hot
backup. Refer to publication 1785-6.5.24 for more
information.
Verify that the PLC-5C is a Series F PLC-5/40C or
-5/80C.
Verify that the 1785-CHBM Hot Backup module is
properly installed.
The target node does not support ControlNet Hot
Backup.
Replace the target node with one that supports
ControlNet Hot Backup.
280 0x0118 INVALID CONFIGURATION FORMAT The target node/module does not match the
node/module entered in the map table.
Replace the target node/module with the correct
node/module.
Verify that the target node/module is powered up.
Correct the map table.
Decimal Code Hex. Code Error Message Explanation/Possible Cause(s) Possible Corrective Action(s)
ControlNet Errors