Troubleshooting
Remote I/O 5-23
troubleshooting – remote I/O system, 1771-ASB series B continued...
See page 5-24 for footnotes.
Indicator
(on I/O rack)
Response Description Probable Cause Recommended Action
Active
Adapter Fault
I/O Rack Fault
Off
Off
Off
If remote I/O
scanner/distribution panel
(1772-SD, -SD2) is in
disable search mode,
then response is normal.
2
power supply fault
wiring from scanner to
adapter module
disrupted
scanner not configured
properly
one faulted chassis
within a rack group
address causing
scanner/distribution
panel to fault all chassis
in rack group address
(when in disable search
mode)
Check power supply, cable connections, and
make sure adapter module is fully seated in
chassis
Correct cable and wiring defects
Refer to publication 1772-2.18 for scanner
configuration
Check sequentially from the first module to the
last module to pinpoint fault; correct any faults
and proceed to the next chassis
Active
Adapter Fault
I/O Rack Fault
Blinking
On
On
module identification line
fault
excessive noise on
backplane
Verify power supply and chassis grounding
ACTIVE
ADAPTER
FAULT
I/O RACK
FAULT