User manual

Switch Settings
Remote I/O Rack Number 4-16
Classic PLC-5
processors only
Remote I/O Rack Number
Classic PLC-5 Processor (except PLC-5/10) as an Adapter in a PLC-5,
Scanner Module, or VME System
Rack 4 5 6 7 8 Rack 4 5 6 7 8
01 on on on on off 15 on off off on off
02 on on on off on 16 on off off off on
03 on on on off off 17 on off off off off
04 on on off on on 20 off on on on on
05 on on off on off 21 off on on on off
06 on on off off on 22 off on on off on
07 on on off off off 23 off on on off off
10 on off on on on 24 off on off on on
11 on off on on off 25 off on off on off
12 on off on off on 26 off on off off on
13 on off on off off 27 off on off off off
14 on off off on on
PLC-5/15, -5/20, -5/20E, -5/20C processors address racks 01-03PLC-5/40, -5/40L, -5/40E, -5/40C processors address racks 01-17
PLC-5/11 processor address rack 3 only (as remote I/O) PLC-5/60, -5/60L, -5/80, -5/80E, -5/80C processors address
PLC-5/25, -5/30 processors address racks 01-07racks 01-27
on = closed
off = open