Switch Settings
Complementary I/O 4-5
I/O Rack Number (without Complementary I/O
1771-ASB series C and series D)
Rack 1 2 3 4 5 6 Rack 1 2 3 4 5 6
01 on on on on on off 15 on on off off on off
02 on on on on off on 16 on on off off off on
03 on on on on off off 17 on on off off off off
04 on on on off on on 20 on off on on on on
05 on on on off on off 21 on off on on on off
06 on on on off off on 22 on off on on off on
07 on on on off off off 23 on off on on off off
10 on on off on on on 24 on off on off on on
11 on on off on on off 25 on off on off on off
12 on on off on off on 26 on off on off off on
13 on on off on off off 27 on off on off off off
14 on on off off on on
PLC-5/15, -5/20, -5/20E, -5/20C processors address racks 01-03 PLC-5/40, -5/40E, -5/40L, -5/40C processors address racks 01-17
PLC-5/11 processor address rack 3 only PLC-5/60, -5/60L, -580, -5/80E, -5/80C processors address racks 01-27
PLC-5/25, -5/30 processors address racks 01-07
on = closed
off = open