QUICK START CLASSIC PLC-5 PROG Instruction Manual

Chapter 4
Publication
178510.3 - October 1996
Troubleshoot the Processor
System
Use
the PLC5 Processor
Status Indicators
(page 4-1)
1
BATT
PROC
FORCE
COMM
Indicator Color Description Probable Cause Recommended Action
PROC green
(steady)
processor in RUN mode and
fully operational
normal operation no action required
green
(blinking)
Processor memory being
transferred to EEPROM
normal operation no action required
red
(blinking)
major fault runtime error Check major fault bit in status file (S:11)
for error definition. Clear fault bit, correct
problem, and return to RUN mode.
red
(steady)
major fault
user RAM has
checksum error
memory module
error
Clear memory and reload program.
Check backplane switch settings
and/or insert correct memory module.
off processor in program load or
TEST mode or is not receiving
power
Check power supply and connections.
PROC
REM I/O
all red
(steady)
internal
diagnostics have
failed
Power down, reseat processor and
power up. Then, clear memory and
reload your program. Replace EEPROM
with new program. Then, if necessary,
replace the processor.
FORCE amber
(steady)
forces enabled normal operation no action required
amber
(blinking)
forces present, but not
enabled
normal operation no action required
off no forces present normal operation no action required
BATT red
(steady)
battery low Replace battery within 12 days (typical).
off battery is good normal operation no action required
ADPT
(continues)
green
(steady)
processor is in adapter mode normal operation no action required
COMM
BATT
REM I/O
ADPT
PROC
FORCE
FAULT
ACTIVE
RUN
REM
R
U
N
P
R
O
G
Use the PLC5 Processor
Status Indicators