User Manual Owner manual
Processor Status File
Appendix B
B-4
This word of
the status file:
Stores:
S:12
(continued)
Fault codes
Code Description
70 duplicate labels
71 SFC subchart is already executing
72 tried to stop an SFC that is not running
73 maximum number of SFC subcharts exceeded
74 SFC file error
75 SFC contains too many active steps
77 SFC references a step, transition, subchart, or SC file that is
missing, empty, or too small
78 SFC could not continue after power loss
79 error in downloading an SFC to a processor that cannot run SFCs
or this specific PLC processor does not support this enhanced
SFC
80 I/O configuration error
81 illegal setting of I/O chassis backplane switch
82 illegal cartridge type
83 user watchdog fault
84 error in userconfigured adapter mode block transfers
85 bad cartridge
86 cartridge incompatible with host
87 rack overlap (includes any adapter channel)
88 scanner channels are overloading the remote I/O buffer; too much
data for the processor to process
90 coprocessor extensive memory test failed
91 coprocessor undefined message type
92 coprocessor illegal pool index
93 coprocessor illegal maximum pool size
94 coprocessor illegal ASCII message
95 coprocessor reported fault
96 coprocessor present signal lost
97 coprocessor illegal minimum pool size
98 coprocessor first/last 16 bytes RAM test failed
99 coprocessor to processor data transfer faulted
100 processor to coprocessor transfer failed
101 coprocessor end of scan transfer failed
102 file number specified for raw data transfer through the coprocessor
is an illegal value
103 element number specified for raw data transfer through the
coprocessor is an illegal value
104 size of the transfer requested through the coprocessor is an
illegal size
105 offset into the raw transfer segment of the coprocessor is an
illegal value
106 coprocessor transfer protection violation
200 ControlNet output transfer missed
201 ControlNet input data missed
202 ControlNet diagnostic data missed
203 ControlNet scheduled transmit data overflow
204 ControlNet configuration too complex for the PLC5 processor
S:13 Program file where fault occurred
S:14 Rung number where fault occurred
S:15 VME status file
S:16 I/O Status File
S:12S:16