User Manual Owner manual

Processor Status File
Appendix B
B-3
This word of
the status file:
Stores:
S:11
Major fault
Bit Description
0 corrupted program file (codes 1019)
1 corrupted address in ladder file (codes 1029)
2 programming error (codes 3049)
3 SFC fault (codes 7179)
4 error while assembling program (code 70)
5 startup protection fault
6 peripheral device fault
7 jumped to fault routine (codes 09)
8 watchdog faulted
9 system configured wrong (codes 8089)
10 recoverable hardware error
11 MCP does not exist or is not ladder or SFC file
12 PII does not exist or is not ladder
13 STI does not exist or is not ladder
14 fault routine does not exist or is not ladder
15 fault routine file is not a ladder file
S:12 Fault codes
Code Description
09 userdefined
10 failed data table check
11 bad user program checksum
12 bad integer operand type
13 bad mixed mode operand type
14 not enough operands for instruction
15 too many operands for instruction
16 bad instruction found
17 no expression end
18 missing end of edit zone
19 download aborted
20 indirect address out of range (high)
21 indirect address out of range (low)
22 attempt to access undefined file
23 file number less than 0 or greater than number of defined files; or
,
indirect reference to file 0, 1, 2; or bad file number
24 indirect reference to wrong file type
30 subroutine jump nesting level exceeded
31 too few subroutine parameters
32 jump to nonladder file
33 CAR routine not 68000 code
34 bad timer parameters entered
35 bad PID delta time entered
36 PID setpoint out of range
37 invalid I/O specified in an immediate I/O instruction
38 invalid use of return instruction
39 FOR loop missing NXT
40 control file too small
41 NXT instruction with no FOR
42 jump target does not exist
43 file is not an SFC
44 error using SFR
45 invalid channel number entered
46 IDI or IDO instruction length operand too long ( > 64 words)
4769 reserved
S:11S:12