Processor Status File
Appendix B
B-2
This word of
the status file:
Stores:
S:3 to S:6
Active Node table for channel 1A
Word Bits DH+ Station #
3 015 0017
4 015 2037
5 015 4057
6 015 6077
S:7 Global status bits:
• low 8 bitsrack fault bits for racks 07
• high 8 bitsrack queuefull bits for racks 07
S:8 Last program scan (in ms)
S:9 Maximum program scan (in ms)
S:10 Minor fault (word 1)
Bit Description
0 battery is missing or low (replace in 12 days)
1 DH+ table has changed (active node table)
2 STI delay too short, interrupt program overlap
3 EEPROM memory transfer at powerup
4 edits prevent SFC continuing
5 invalid I/O status file
6 memory-cartridge battery low
7 no more command blocks exist
8 not enough memory on the memory module to upload the
program from the processor
9 no MCP is configured to Run
10 MCP not allowed
11 PII word number not in local rack
12 PII overlap
13 no command blocks exist to get PII
14 arithmetic overflow
15 SFC action overlap
S:310