User Manual Owner manual
Chapter 5
Monitoring and Troubleshooting Your
ControlNet System
5-10
Do this:If you want to:
clear the inhibit bit so that the processor
will attempt to establish a connection with
the module or message
1. Move the cursor to the Inhibit field for that entry
2. Type a
0
3. Press [Enter]
set the reset bit so that the processor will
set the output module or message's
Run/Program command to Program
mode
1. Move the cursor to the Reset field for that entry
2. Type a
1
3. Press [Enter]
clear the reset bit so that the processor
will set the output module or message's
Run/Program command to the
processor's mode
1. Move the cursor to the Reset field for that entry
2. Type a
0
3. Press [Enter]
return to the ControlNet I/O Mapping
(Monitor) screen
Press [Esc]