User Manual Owner manual

Chapter 3
Configuring Your ControlNet System
3-10
Editing ControlNet 1794 I/O Module Action
Follow the steps on the left to the ControlNet I/O Action (Edit) screen.
Important: Only one user on a network can enter a processors
ControlNet 1794 I/O Module Action screen at one time.
ControlNet – I/O Action EDIT
Channel 2 Configuration NODE 1
Node 4 1794–ACN
Module Type Fault Action Idle Action Fault Action
Slot From Idle
0 1794–Digital Reset Reset Idle
1 1794–IE8/A Reset Reset Idle
2 1794–OE4/A Safe Reset Idle
3 1794–IE4XOE2/A Safe Reset Idle
4 1794–Digital Reset Reset Idle
5 1794–Digital Reset Reset Idle
6 1794–Digital Reset Reset Idle
7 1794–Digital Reset Reset Idle
Press a function key or cursor key.
>
Rem Prog Forces:None 5/40C File CN
Accept Map Toggle Toggle
Edits Edit All Entry
F1 F2 F8 F10
If you want to: Do this:
change a system's fault action
i.e., the action that it takes
when it faults
1. Move the cursor to the Fault
Action column
2. Press
[F8]—Toggle All
to toggle between:
Resetto change all outputs to zero
Hold
Lastto maintain all current output values
Safeto change all outputs to userspecified fail-safe values
change a system's idle action
i.e., the action that it takes
when it becomes idle
1. Move the cursor to the Idle
Action column
2. Press
[F8]—Toggle All
to toggle between:
Resetto change all outputs to zero
Hold
Lastto maintain all current output values
Safeto change all outputs to userspecified fail-safe values
change a system's fault action
from idlei.e., the action that
it takes when it faults from idle
1. Move the cursor to the Fault
Action
From
Idle column
2. Press
[F8]—Toggle All
to toggle between:
Idleto use the idle action
Faultto use the fault action
change a module's fault action
i.e., the action that it takes
when it faults
1. Move the cursor to the module's field Fault
Action field
2. Press
[F10]—Toggle Entry to toggle between:
Resetto change all outputs to zero
Hold
Lastto maintain all current output values
Safeto change all outputs to userspecified fail-safe values
Channel
Overview
Channel
Configuration
6200
Main Menu
General
Utility
F3
Online
Program
Offline
Program
F1
F7
or
F4
F5
(Monitor)
Map
Monitor
F2
Map
Edit
F2
Edit
Actions
F9
Move cursor to
Channel 2: CONTROLNET
Move cursor to
a 1794 I/O entry