Chapter 2
Planning to Use Your ControlNet
PLC5 Processor
2-16
If they fit and are:
Can be run on a
PLC5/20C or
5/40C channel:
On channel:Archived from a:
Program files
for this process:
I/O
PLC5/20E
PLC 5/40E
PLC5/60L
PLC 5/80E
2
1A or 1B
performed by remote I/Oyou must make these
changes manually by reprogramming
I/O
PLC5/40E
PLC5/40L
PLC5/80E
2
performed by the ControlNet networkyou must make
these changes manually by reprogramming
③④⑤
These include processor files, datatable files, and port configurations.
If you do not update the program, the ControlNet processor will fault.
You must change blocktransfer instructions for the ControlNet system from the standard block transfer read (BTR) and block transfer write (BTW)
instructions to scheduled transfers or to unscheduled CIO instructions.
You must edit nonControlNet PLC5 programs containing references to the I/O Status File for use with I/O connected via the ControlNet network.
Information regarding ControlNet status is stored in a separate data file that you specify through the 6200 PLC5 Programming Software.
If you do not update the program, the datatable locations corresponding to the missing" I/O devices will not be updated.