User Manual Owner manual
Chapter 2
Planning to Use Your ControlNet
PLC5 Processor
2-11
Table 2.G
1771
Nondiscrete I/O DataT
ransfer Mapping
Module Type
Description
①②
Default
Entries
per Module
Default
Input
Size
Valid
Input
Size(s)
Default
Output
Size
Valid
Output
Sizes
Default
Config.
Size
Valid
Configuration
Sizes
1771-CFM/A
1771CFM/A Configurable
Flowmeter Module
2 41 041 60 04, 14, 24,
34, 44, 48,
52, 56, 60
60 04, 14, 24, 34,
44, 48, 52, 56,
60
1771-DE/A
1771DE/A Absolute Encoder Module 2 2 0, 2 20 0, 5, 10, 15,
20, 22
20 0, 5, 10, 15, 20,
22
1771-IE
1771IE Analog Input Module 1 8 18
1771-IF
1771IF Analog Input Module 1 8 164
1771-IFE/A
1771IFE/A Analog Input Module 1 20 520 37 0, 3, 37
1771-IFE/B
1771IFE/B Analog Input Module 1 20 522 37 0, 3, 37, 39
1771-IJ
1771IJ Encoder/Counter Module
2
1
01
3
0
3
3
0
3
1771-IK
1771IK Encoder/Counter Module
2 1 0, 1 3 03 3 03
1771-IL/A
1771IL/A Isolated Analog Input Mod. 1 12 512 19 0, 2, 19
1771-IL/B
1771IL/B Isolated Analog Input Mod. 1 12 515 19 0, 2, 19, 36, 37
1771-IR/A
1771IR/A RTD Input Module 1 8 38 14 0, 2, 8, 14
1771-IR/B
1771IR/B RTD Input Module 1 8 39 14 0, 2, 8, 14, 15
1771-IS
1771IS Multiplexer Input Module 1 6 17
1771-IXE/A
1771IXE/A Thermocouple/Millivolt
Input Module
1 12 412 27 0, 1, 19, 27
1771-IXE/B
1771IXE/B Thermocouple/Millivolt
Input Module
1 12 413 27 0, 1, 19, 27, 28
1771-IXHR/A
1771IXHR/A Highresolution
Thermocouple/Millivolt Input Module
1 12 413 27 0, 3, 19, 27, 28
1771-OF
1771OF Analog Output Module 2 1 01 4 460
1771-OFE/A
1771OFE/A Analog Output Module
2
5
05
13
1
513
13
0513
1771-OFE/B
1771OFE/B Analog Output Module
2 5 0, 5 13 15, 13 13 0, 5, 13
N-Series/A
1771 NSeries Analog Module 2 28 0, 2028 59 0, 29, 59 59 0, 29, 59
1771-QA
1771QA Stepper Positioning Module 1 4 110
1771-QB
1771QB Linear Positioning Module 1 5 133
1771-QC
1771QC Servo Positioning Module 1 6 114
1771-SN
1771SN Sub I/O Scanner Module 2 16 0, 763 16 0, 763
1771-VHSC/A
1771VHSC Very Highspeed
Counter Module
2 18 0, 426 64 02, 4, 12, 20,
24, 29, 34,
39, 44, 49,
54, 59, 64
64 02, 4, 12, 20,
24, 29, 34, 39,
44, 49, 54, 59,
64
1771-Generic
1771 Generic Module
③
1 1 064 1 064 1 064
①
ENPT Default = 4 x NUT
②
ENPT Range = 215000 ms
③
For newly released modules or modules that can have multiple configurations but only one configuration is being used, you can use the generic
module type and specify the input and/or output sizes.