User Manual Owner manual
Chapter 1
Installing Your ControlNet PLC5 Processor
1-18
This section lists information about:
serial cables
DH+ programming cables
remote I/O cables
ControlNet cables
For more information about cables, see the Enhanced and Ethernet PLC-5
Programmable Controllers User Manual, publication 1785-6.5.12.
Serial Cables
You can make your own serial cables or purchase them from
Allen-Bradley Company, Inc.
The side label of the processor shows the following table, which
lists Channel 0 (serial port) pin assignments.
Pin RS232C RS422A RS423 Pin RS232C RS422A RS423
1
C.GND C.GND C.GND 14 NOT USED TXD.OUT
+
SEND COM
2 TXD.OUT TXD.OUT
TXD.OUT 15
3 RXD.IN RXD.IN
RXD.IN 16 NOT USED RXD.IN
+
REC COM
4 RTS.OUT RTS.OUT
+
RTS.OUT 17
5 CTS.IN CTS.IN
+
CTS.IN 18
6 DSR.IN DSR.IN DSR.IN 19 NOT USED RTS.OUT
NOT USED
7 SIG.GND SIG.GND SIG.GND 20 DTR.OUT DTR.OUT DTR.OUT
8 DCD.IN DCD.IN DCD.IN 21
9 22 NOT USED DSR.IN NOT USED
10 NOT USED DCD.IN NOT USED 23 NOT USED DTR.OUT NOT USED
11 24
12 25
13 NOT USED CTS.IN
NOT USED
The shading indicates that the pin is reserved.
This processor’s serial port can support these configurations:
Digital Interface Maximum Cable Length
RS232C
15 m (approximately 50 ft)
RS422A (compatible) 61 m (approximately 200 ft)
RS423 61 m (approximately 200 ft)
Selecting Appropriate
Cables