Chapter 1
Installing Your ControlNet PLC5 Processor
1-9
Replacing the Battery
Replace the lithium battery every year or when the BATT status indicator
is red. For estimated battery lifetimes, see the table below:
Processor Temperature
WorstCase BatteryLife Estimates
Power Off 100% Power Off 50%
Battery Duration
PLC5/20C
60°C
218 days 1.17 years 3.7 days
25°C
1.7 years 3.34 years 15 days
PLC5/40C
60°C
105 days 207 days 40 hours
25°C
1.3 years 2.57 years 10.8 days
The battery status indicator (BATT) warns you when the battery is low. These durations are
based on the battery supplying the only power to the processorpower to the chassis is
offonce the status indicator first lights.
Disposing of the Battery
Do not dispose of lithium batteries in a general trash collection when their
combined weight is greater than or equal to 0.5 gram. A single 1770-XYC
battery contains 0.65 grams of lithium. Check your state and local
regulations that deal with the disposal of lithium batteries.
ATTENTION: Follow these precautions:
Do not incinerate or expose the battery to
high temperatures.
Do not solder the battery or leads; the battery
could explode.
Do not open, puncture, or crush the battery. The
battery could explode or toxic, corrosive, and
flammable chemicals could be exposed.
Do not charge the battery. An explosion may result,
or the cell may overheat and cause burns.
Do not short positive and negative terminals together.
The battery will heat up.
Tip
You can insert or remove the
battery without powering down
the processor. If you do not
want to lose your program,
make sure that the processor
is powered when replacing
the battery.