User Manual Owner manual

Chapter 1
Installing Your ControlNet PLC5 Processor
1-4
Figure 1.1 and Figure 1.2 show the front panels of the ControlNet
PLC-5 processors.
Figure 1.1
PLC5/20C
Processor Front Panel
Battery Status Indicator
(Red)
Processor RUN/FAULT Status Indicator
(Green/Red)
Force Status Indicator
(Amber)
Channel
0 Communication
ACTIVE/F
AULT
Status Indicator
(Green/Red)
Memory Module Space
Battery Compartment
Use this port with ASCII or DF1 fullduplex, half
duplex master, and halfduplex slave protocols.
The port's default configuration supports processor
programming:
Keyswitchselects processor mode
Channel 0
Serial Port25pin Dshell; supports standard EIA
RS232C and RS423; is RS422A compatible
DH+ Programming Terminal Connection
to Channel 1A
8pin miniDIN
one stopbit
BCC error check
no handshaking
DF1 pointtopoint
2400 bit/s
no parity
Channel 2 ControlNet Status Indicators
(Green/Red)
Channel 2
ControlNet Redundant Media Ports
BNC; dedicated
Channel 0 is optically coupled (provides high electrical
noise immunity) and can be used with most RS422A
equipment as long as:
termination resistors are not used
the distance and transmission rate are reduced to
comply with RS423 requirements
ControlNet I/O Status Indicator
(Green/Red)
ControlNet Network Access Port
(NAP)RJ45 connector
Channel 1 Status Indicators (Green/Red)
Channel 1A
3 pin; dedicated DH+
Channel 1B
3 pin; default is remote I/O scanner;
configurable for:
remote I/O scanner
remote I/O adapter
DH+ communication
unused
Identifying ControlNet PLC5
Processor Components