User guide
most significant octal digit = 6
least significant octal digit = 4
Installing the 1785KA5
Communication Adapter Module
Chapter 2
2-6
Setting the DH+ Station Address
Set switches 3-8 of SW-2 to the DH+ station address for the 1785-KA5.
Valid addresses are 0-77 octal Set the switches as follows:
Most significant octal digit (switches 35)
To set to Set switch 3 to Set switch 4 to Set switch 5 to
0 0 0 0
1 0 0 1
2 0 1 0
3 0 1 1
4 1 0 0
5 1 0 1
6 1 1 0
7 1 1 1
Least significant octal digit (switches 68)
To set to Set switch 6 to Set switch 7 to Set switch 8 to
0 0 0 0
1 0 0 1
2 0 1 0
3 0 1 1
4 1 0 0
5 1 0 1
6 1 1 0
7 1 1 1
For example
To set the module’s DH+ station address to 64 octal, set the switches as
shown below:
Set switch To
3 1
4 1
5 0
6 1
7 0
8 0