Installation Instructions Instruction Manual

Interpret the LED Indicators 6-3
Publication 1784-IN003D-EN-P - January 2006
Steady red Faulted card Check operating system event log for details
of fault (if the personal computer’s operating
system supports an event log)
Cycle power to the computer
Verify that you have firmly inserted the
1784-PCIC or 1784-PCICS card into a PCI local
bus expansion slot and that the expansion
slot screw is tightened
If fault persists, contact your Rockwell
Automation representative or distributor
Alternating red/green Self-test
Incorrect channel
configuration
None
Verify that the ControlNet network is
connected to the correct channel of the
1784-PCIC or 1784-PCICS card (
for example,
if the ControlNet network is configured for
channel A
only, then the card must be
connected to the network via channel A)
Alternating red/off Incorrect node
configuration
Duplicate
ControlNet node
address
Check 1784-PCIC or 1784-PCICS node
address and other ControlNet configuration
parameters
A or B
Cause Action
Off Channel disabled Use RSNetWorx for ControlNet sofware to
configure the ControlNet network for
redundant media, if required
Steady green Normal operation None
Flashing green/off Temporary
network errors
Check media for broken cables, loose
connectors, or missing terminators
If condition persists, refer to the ControlNet
Media Planning and Installation Manual,
publication CNET-IN002
Flashing red/off Media fault Check media for broken cables, loose
connectors, or missing terminators
If condition persists, refer to the ControlNet
Media Planning and Installation Manual,
publication CNET-IN002
Table 6.1 ControlNet status interpretation
A and B
Cause Action