User manual

Publication 1747-UM011F-EN-P - May 2007
Selecting Your Hardware Components 37
SLC Communication Options
Communication
Protocol
Processor
SLC 5/01 SLC 5/02 SLC 5/03 SLC 5/04 SLC 5/05
DH-485 peer-to-peer receive only receive and initiate receive and initiate
DH-485 via RS232
port
——
receive and initiate
(9)
receive and initiate
(9)
receive and initiate
(9)
DF1 via RS232 port
(full-duplex or
half-duplex master
or slave)
receive only
(1)
receive only
(1)
receive and initiate receive and initiate receive and initiate
ASCII via RS232 port receive and initiate receive and initiate receive and initiate
Data Highway Plus
(DH+)
receive only
(2)
receive only
(2)
receive and initiate
(5)
receive and initiate
receive and initiate
(5)
Ethernet
receive and initiate
(6)
receive and initiate
(6)
receive and initiate
DeviceNet
receive and
initiate
(3)
receive and
initiate
(3)(7)
receive and
initiate
(3)(7)
receive and
initiate
(3)(7)
ControlNet
receive and
initiate
(4)
receive and
initiate
(4)(8)
receive and
initiate
(4)(8)
receive and
initiate
(4)(8)
(1)
A 1747-KE or 1770-KF3 interface is required to bridge from DF1 (full-duplex or half-duplex slave only) to DH485 network.
(2)
A ControlLogix gateway with a 1746-DHRIO interface and a 1756-DH485 interface is required to bridge from DH+ to DH-485 network.
(3)
A 1747-SDN module is required for scanning I/O and for explicit messaging on DeviceNet network.
(4)
A 1747-SCNR module is required for scanning I/O and for explicit messaging on ControlNet network.
(5)
The SLC 5/04s channel-to-channel passthru feature may be used to bridge between DH+ and DH-485 network or between DH+ and DF1 full-duplex network (DH+ to DF1
full-duplex passthru available starting with OS401). Another option is to use the 1785-KE interface to bridge between DH+ and DF1 full-duplex or DH+ and DF1 half-duplex
master/slave network.
(6)
A 1761-NET-ENI interface is required to bridge from DF1 full-duplex to Ethernet network.
(7)
A 1761-NET-DNI interface is required to bridge from DF1 to DeviceNet network.
(8)
A 1747-KFC15 module or 1770-KFC15 interface is required to bridge from DF1 to ControlNet network.
(9)
If using 1747-AIC interface for isolation, connect to DH-485 network using 1747-PIC interface. If using a 1761-NET-AIC interface for isolation, connect directly to DH-485
network with 1747-CP3 serial cable (or equivalent RS-232 null-modem cable).
TIP
The 1785-KE module requires the use of a 1771 series chassis
and power supply.