User manual

Publication 1747-UM011F-EN-P - May 2007
26 Quick Start for Experienced Users
1. Set the communication parameters of software to match the
default parameters of the processor.
9. Establish communication to the processor. Reference
Refer to the following to establish communication between the processor and your
personal computer.
Chapter 8
(Starting Up Your
Control System)
Processor Procedure
SLC 5/01 Connect 1747-PIC interface from the processor to your personal computer
serial port or connect 1747-UIC interface from the processor to your
personal computer USB port, or use a 1784-PKTX(D) or 1784-PMCK
interface.
SLC 5/02 Connect 1747-PIC interface from the processor to your personal computer
serial port or connect 1747-UIC interface from the processor to your
personal computer USB port, or use a 1784-PKTX(D) or 1784-PMCK
interface.
SLC 5/03 Connect the 1747-PIC interface from the processor to your personal
computer serial port or connect the 1747-UIC interface from the processor
to your personal computer USB port to the processor by using the
1747-C13 or 1747-CP3 cable. You can also use a 1784-PKTX(D) or
1784-PCMK interface, or a 1747-CP3 cable from channel 0 of the
processor to the personal computer serial port.
SLC 5/04 Connect a 1747-CP3 cable from channel 0 of the processor to the personal
computer serial port or connect the 1747-UIC interface from channel 0 of
the processor to your personal computer USB port, or use a 1784-PKTX(D)
or 1784-PCMK interface.
SLC 5/05 Connect a 1747-CP3 cable from channel 0 of the processor to the personal
computer serial port, or connect the 1747-UIC interface converter from
channel 0 of the processor to your personal computer USB port. For
Ethernet connection, connect channel 1 of the processor and the PC
Ethernet card to an Ethernet hub by using 10/100Base-T compatible
cable.
(1)
(1)
EtherNet/IP address must first be set via BOOTP or an RS-232 connection. See appendix C for more information.
Comms Channel Channel 0
Configuration
Channel 1 Configuration
SLC 5/01 and 5/02 SLC 5/03, 5/04, and 5/05 SLC 5/03 SLC 5/04 SLC 5/05
DH-485:
19.2 Kbaud
node address = 1
DF1 Full-duplex:
no handshaking
19.2 Kbaud
CRC Error Check
duplicate packet,
detect on
no parity
DH-485:
19.2 Kbaud
node address = 1
DH+:
57.6 Kbaud
node address = 1
Ethernet:
BOOTP enabled