User manual

Publication 1747-IN011F-EN-P - May 2007
238 Control Networks
A single scanner (master) can communicate with up to 63 nodes
(slaves) on DeviceNet. The SLC system supports multiple scanners if
more devices are required to be controlled by a single SLC 500
processor.
DeviceNet Network
The 1761-NET-DNI DeviceNet Interface
The DeviceNet Interface (DNI) is an intelligent DeviceNet-to-DF1
protocol conversion device that let existing DF1 devices communicate
on DeviceNet network. The DF1 device is able to exchange I/O data
with a master device and is able to initiate and receive DF1
encapsulated DeviceNet messages across a DeviceNet network.
The DNI provides a single DeviceNet connection point and a single
RS-232 connection. The DeviceNet port is isolated from the DNI
digital logic and RS-232 port.
The primary functions of the DNI are:
to collect and receive input data from the DF1 device connected
on its RS-232 port and forward that data to a connected master
on a DeviceNet network.
to monitor output data received from the DeviceNet master and
write that data to the DF1 device.
to let DF1 devices send and receive messages across the
DeviceNet network.
The DNI can be used to interconnect:
MicroLogix controllers.
SLC 5/02 or later
processor
1747-SDN Scanner
1770-KFD Interface
Personal
Computer with
RSNetworx for
DeviceNet
Software
RS-232
cable
DeviceNet
Devices
RediSTATION
Panel
1305 Drive
Flex I/O Controller
DeviceNet Network