Setting Up the DH+ Network 227
Minimizing Noise
To minimize the affect of noise on the SLC 5/04 processor, ground the
cable shields to earth via 0.01μF capacitors as shown in the DH+
wiring example below. Only directly ground the shield at one point
on the network.
SLC 5/04 CPU
PROC
PROG
FORCE
COMM
BATT
RUN
R
E
M
PLC±5/20
PROGRAMMABLE
CONTROLLER
1
2
1
2
AB
SLC 5/04 CPU
1
2
RUN PROG
FORCE
RS232
BATT
DH+
FLT
RUN
REM
RUN PROG
FORCE
RS232
BATT
DH+
FLT
RUN
REM
Clear
Shield
Blue
Clear
Shield
Blue
Clear
Shield
Blue
Terminating
Resistor
Terminating
Resistor
Connector Connector Connector
Belden #9463 Cable
Belden #9463 Cable
0.01μF
Shield
(1)
Shield
0.01μF
Shield
Earth Ground
Earth Ground
Earth Ground
(1) To chassis ground directly at one point only in the network.