156 Troubleshooting
Power status indicator
is on
Run status indicator is
on
Force status indicator is
on
All other status
indicators are off
Status of any
Communication status
indicator does not
matter
System does not
operate per ladder
logic
User forced I/O is
disabling operation.
1. Monitor program file on-line and identify forced I/O.
2. Disable appropriate forces and test system conditions again.
Power status indicator
is on
Run status indicator is
on
Force status indicator is
flashing
All other status
indicators are off
Status of any
Communication status
indicator does not
matter
System does not
operate per
programmed
forces
User programmed
forces are not
enabled.
1. Monitor program file on-line and identify programmed
forces.
2. Enable appropriate forces and test system conditions again.
Once forces are enabled, the Force status indicator turns on
(steady).
Power status indicator
is on
FLT status indicator is
flashing
Batt status indicator is
on
All Other status
indicators are off
Status of any
Communication status
indicator does not
matter
CPU major error
with low or no
battery back-up
Loss of RAM during
power-down.
1. Verify battery is connected. See page 139.
2. Replace the battery if you want RAM battery backup. See
page 139.
3. Refer to processor major fault recommended action steps.
SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors
If the status indicators
indicate
The following
error exists
Probable Cause Recommended Action