User manual

113 Publication 1747-UM011F-EN-P - May 2007
Chapter
7
Wiring Your I/O Modules
This chapter describes how to wire your I/O modules. It covers the
following:
Defining sinking and sourcing
Preparing your wiring layout
Features of an I/O module
Recommendations for wiring I/O devices
Wiring your I/O modules
Octal label kit installation
Using removable terminal blocks
Defining Sinking and
Sourcing
Sinking and sourcing are terms used to describe a current signal flow
relationship between field input and output devices in a control
system and their power supply.
Field devices connected to the positive side (+V) of the field
power supply are sourcing field devices.
Field devices connected to the negative side (dc Common) of
the field power supply are called sinking field devices.
To maintain electrical compatibility between field devices and the
programmable controller system, this definition is extended to the
input/output circuits on the discrete I/O modules.
Sourcing I/O circuits supply (source) current to sinking field
devices.
Sinking I/O circuits receive (sink) current from sourcing field
devices.
Europe: dc sinking input and sourcing output module circuits are the
commonly used options.