Configure a ControlNet Module 3-13
Schedule the Network Offline
The following instructions assume that:
your RSLogix 5000 project uses 1 controller and 1 network. We
recommend that you use only one (1) 1756-CN2 or 1756-CNB module
in the local chassis when scheduling the network offline.
your RSLogix 5000 project is complete but has not been downloaded to
the controller.
If your network has already been scheduled and you made a change to it, you
must reschedule it. Refer to the section Rescheduling a ControlNet Network
That Has Previously Been Scheduled for more information.
1. In your RSLogix 5000 project, access the local ControlNet module’s
properties.
A.Right-click on the local ControlNet
communication module.
B.Click Properties.