User manual
Publication CNET-UM001C-EN-P - November 2005
3-10 Configure a ControlNet Module
Download the Project to the Logix5000 Controller
When you finish adding the local and remote ControlNet communication 
modules to your RSLogix 5000 project, you must download the new 
configuration to your Logix5000 controller.
1. Because you must schedule the ControlNet network (explained in the 
following section) before using the new configuration, switch your 
Logix5000 controller to Program mode in one of the following ways:
• Turn the controller keyswitch to PROG.
• Turn the controller keyswitch to REM and use RSLogix 5000 
software to change the controller to Remote Program mode.
2. Use the Who Active button to begin the download process.
IMPORTANT
Before you your RSLogix5000 project configuration to 
your ControlNet Communication modules, consider 
whether you will schedule the ControlNet network offline 
or online.
• If you are going to schedule the network offline, 
complete the steps beginning in the section Schedule 
the Network Offline before downloading 
configuration.
• If you are going to schedule the network online, 
complete the steps beginning below and then move to 
the section Schedule the Network Online.
Click Who Active.