1-12 About the Logix5000 ControlNet Communication Modules
This table lists the possible bridges between communication networks.
Table 1.3 Bridges Between Communication Networks
To Bridge
From This
Network
To This
Network:
You Can Use the Following
(1)
In a CompactLogix System In a ControlLogix Chassis In a FlexLogix Controller
ControlNet DeviceNet 1769-L32C or 1769-L35CR
controller
1769-SDN scanner
or
1769-L32C or 1769-L35CR
controller
one 1788-CN2DN
module
(2)
1756-CN2(R) module
1756-CNB(R) module
1756-DNB module
1788-CN(x) card
1788-DNBO card
or
1788-CN(x) card
one 1788-CN2DN
module
(2)
EtherNet/IP NA 1756-CN2(R) module
1756-CNB(R) module
1756-ENBT module
1788-CN(x) card
1788-ENBT card
EtherNet/IP ControlNet NA 1756-ENBT module
1756-CN2(R) module
1756-CNB(R) module
1788-ENBT card
1788-CN(x) card
DeviceNet 1769-L32E or 1769-L35E
controller
1769-SDN scanner
or
1769-L32E or 1769-L35E
controller
one 1788-EN2DN
module
(3)
1756-ENBT module
1756-DNB module
1788-ENBT card
1788-DNBO card
or
1788-ENBT card
one 1788-EN2DN
module
(3)
(1)
You can bridge from a ControlNet network to an Ethernet network and from an Ethernet network to a ControlNet via a SoftLogix virtual chassis. However, the products and
methods you must use to do so are more detailed than can be effectively described in this table. For more information on how to bridge from one network to another via a
SoftLogix virtual chassis, see the SoftLogix5800 System User Manual, publication number 1789-UM002.
(2)
Can serve as a dedicated standalone bridge from ControlNet to DeviceNet.
(3)
Can serve as a dedicated standalone bridge from EtherNet/IP to DeviceNet.