User manual
Publication CNET-UM001C-EN-P - November 2005
Control 1771 I/O Over ControlNet D-3
2. Configure the 1771-ACN(R)15 module.
A.Name the module.
B.Select a Comm Format. For more
information on choosing a Comm Format,
see section Communication Format.
C. Select the module’s Revision level.
D.Select an Electronic Keying level. For
more information on choosing a keying
level, see table Electronic Keying
Options.
I. Set the RPI rate.
The RPI must be equal to or greater than
the NUT. This parameter only applies if
the module uses one of the Rack
Optimized communication formats.
J. Inhibit the module, if necessary.
Initially, do you
want the module to
communicate with
the controller?
Then
Yes Leave the box
unchecked
No Check the
box
(1)
(1)
When you test this portion of the system,
clear the check box.
K. Determine if you want a major fault on the controller if
the connection to the PanelView fails in Run Mode.
If You Want The
Controller To
Then
fault (major fault) Select the check box
continue operating Leave the check box
unchecked
(1)
(1)
Monitor the connection using ladder logic.
L. Click Finish.
E. Select the module’s nod
e
number on ControlNet.
F. Select the Input Size.
G.Select the Output Size.
H.Click Next.