User manual

Publication CNET-UM001C-EN-P - November 2005
C-20 Determine Your ControlNet Media Requirements
Application Considerations
The guidelines in this section coincide with the guidelines for “the installation
of electrical equipment to minimize electrical noise inputs to controllers from
external sources” in IEEE standard 518-1982. When planning your cable
system there are certain installation considerations depending on your
application. There are three categories of conductors:
Table C.3 Conductor Categories
Category Includes
1 ac power lines
high-power digital ac I/O lines
high-power digital dc I/O lines
power connections (conductors) from motion drives to motors
2 analog I/O lines and dc power lines for analog circuits
low-power digital ac/dc I/O lines
low-power digital I/O lines
ControlNet communication cables
3 low-voltage dc power lines
communication cables to connect between system components
within the same enclosure
ATTENTION
These guidelines apply only to noise coupling. Intrinsic
safety requirements for cable mounting are of the highest
priority.