C-6 Determine Your ControlNet Media Requirements
Determine What Type of
Cable You Need
There are several types of RG-6 quad shield cable that may be appropriate for
your installation, depending on the environmental factors associated with your
application and installation site.
Table C.2 Determine Cable Types
IMPORTANT
You should install all wiring for your ControlNet cable
system in accordance with the regulations contained in the
National Electric Code (or applicable country codes), state
codes, and applicable municipal codes. All metal
connectors must be insulated from the ground.
For Use This Cable Type
Light industrial applications Standard-PVC CM-CL2
Heavy industrial applications Lay-on Armoured and
Interlocking Armour
High and low temperature applications, as well as corrosive
areas (harsh chemicals), low smoke generation and low
flame spread
Plenum-FEP CMP-CL2P
Festooning or flexing applications High Flex
Moisture resistant applications; direct burial, with flooding
compound, fungus resistant
Flood Burial