User manual

Publication CNET-UM001C-EN-P - November 2005
8-4 Troubleshoot Your ControlNet Communication Modules
Network Channel Status Indicator Interpretation
Steady - indicator is on continuously in the defined state.
Alternating - the two indicators alternate between the two defined states
at the same time (applies to both indicators viewed together). The two
indicators are always in opposite states, out of phase.
Flashing - the indicator alternates between the two defined states
(applies to each indicator viewed independent of the other). If both
indicators flash, they must flash together, in phase.
SW
ERR
Node address switch changed after power-up. None required, but we recommend that you
either return switches to their original settings
or replace the module, since this could indicate
a latent hardware problem.
Flashing Green OK Normal operation. No connections to or through the module. No
action required
CNFG
ERR
ControlNet configuration error. Recheck configuration.
NET
ERR
Network cabling error or no other active nodes
on network.
Re-check your network cabling and make sure
another node on the network is active (online).
(1)
If switches are set to 00 the display scrolls “FAULT: ADDRESS SWITCHES = 00, ILLEGAL”
If the OK
Indicator Is
With This
Module Status
Display
It Means Take This Action
IMPORTANT
When you connect the module to a ControlNet network
using only the NAP, the LEDs are meaningless.