User manual

Publication CNET-UM001C-EN-P - November 2005
Peer-to-Peer Messaging 6-11
EXAMPLE
Communication path from a Logix5000 controller to a PLC5 controller
over a ControlNet network
Path = 1, 1, 2, 1
ControlNet Network
5
5
5
0
C
N
2
PLC5-C
Node Address = 1
Message
Node Address = 7
Where Indicates
1 connection to the backplane in local chassis
1 slot number of 1756-CN2 module in local chassis
2 connection to port 2 of the 1756-CN2 module (get on ControlNet)
1 node address of remote PLC5