Publication CNET-UM001C-EN-P - November 2005
Peer-to-Peer Messaging 6-9
Message Type to Configure a MSG to an SLC 500 Processor
write (send) the data Message Type CIP Data Table Write
Source Tag first element of the tag (controller-scoped) in this controller that
contains the data
Number of Elements number of elements to transfer
Destination Element first element of the tag for the data in the other controller
Table 6.5 Message Type to Configure a MSG to Logix5000 Controller
If You Want To For This Item Type or Select
Table 6.6 Message Type to Configure a MSG to an SLC 500 Processor
If The Data Is And You Want To For This Item Type or Select
integer (s) read (receive) data Message Type SLC Typed Read
Source Element data table address in the SLC 500 controller, such as N7:10
Number of Elements number of integers to transfer
Destination Tag first element of int_buffer
write (send) data Message Type SLC Typed Write
Source Tag first element of int_buffer
Number of Elements number of integers to transfer
Destination Element data table address in the SLC 500 controller, such as N7:10
floating-point (REAL) read (receive) data Message Type SLC Typed Read
Source Element data table address in the SLC 500 controller, such as F8:0
Number Of Elements number of values to transfer
Destination Tag first element of the tag (controller-scoped) in this controller
for the data
write (send) data Message Type SLC Typed Write
Source Tag first element of the tag (controller-scoped) in this controller
that contains the data
Number Of Elements number of values to transfer
Destination Element data table address in the SLC 500 controller, such as F8:0