Installation Instructions Instruction Manual
Stratix 2000 Ethernet Unmanaged Switches 25
Rockwell Automation Publication 1783-IN001D-EN-P - January 2011
Wiring category
(1)
2 - on power ports
2 - on communication ports
North American temp code T4
IEC temp code T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - Stratix 2000 Switches
Attribute 1783-US03T01F, 1783-US06T01F, 1783-US05T,
1783-US08T
Temperature, operating
• IEC 60068-2-1 (Test Ad,
Operating Cold)
• IEC 60068-2-2 (Test Bd,
Operating Dry Heat)
• IEC 60068-2-14 (Test Nb,
Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, nonoperating
• IEC 60068-2-1 (Test Ab,
Unpackaged Nonoperating
Cold)
• IEC 60068-2-2 (Test Bb,
Unpackaged Nonoperating
Dry Heat)
• IEC 60068-2-14 (Test Na,
Unpackaged Nonoperating
Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
• IEC 60068-2-30 (Test Db,
Unpackaged Damp Heat)
5…95% noncondensing
Vibration
• IEC 60068-2-6 (Test Fc,
Operating)
2 g @ 10…500 Hz
Technical Specifications - Stratix 2000 Switches
Attribute 1783-US03T01F, 1783-US06T01F, 1783-US05T,