User Manual PLC-3 BACKUP CONC(OR.DU1 Owner's manual
Using the 1775MX
Memory Communication Module
Chapter 4
4-6
The MCM OPERATION menu contains an entry for each LIST function
listed in Table 4.D. These functions are a subset of those available when
using message instructions.
Table 4.D
LIST
Functions
Command Description
INACTIVE The memory communication module stops both continuous
data transfers and continuous file transfers to the backup
processor.
FILE
TRANSFER
The memory communication module transfers the selected
files from the primary to the backup processor continuously.
FILE
SELECTION
Lets you select up to 16 files for use with the file transfer
function.
DATA
TABLE XFER
The memory communication module continuously transfers
the entire data table, except the data table status section,
from the primary to the backup processor.
MEMORY
DOWNLOAD
The memory communication module stops any data transfer
in progress and transfers the entire contents of PLC3
memory from the primary to the backup processor.
LOCK
SYSTEM
The memory communication module has the edit resource
for both the primary and backup processors. This protects
the ladder program in the current context from being edited
while in the run or test mode.
UNLOCK
SYSTEM
The memory communication module releases the edit
resource for both the primary and backup processors.
ENABLE
PROG COMP
The memory communication module compares the ladder
diagram program in the backup processor with the one in the
primary processor on a wordbyword basis.
DISABLE
PROG COMP
The memory communication module prevents the execution
of the program compare function.
PROG
COMP LIMITS
Lets you select specific sections of the ladder program to be
compared when ENABLE
PROG COMP
has been
selected.
BACKUP
TO PRIMARY
DATA TRANSFER
Lets you transfer up to 16 words from the backup to the
primary processor.
The following sections describe each LIST command in detail.