User Manual

1–2
Overview of the Very High Speed Counter Module
returns in status either count or frequency in binary or BCD
format
input counts as high as 999,999
up to 500KHz in period/rate or rate measurement frequency
modes
outputs can be tied to any counter
each output has a user-selectable on-off value
outputs can be tied back to an input for cascading
automatic default configuration
each counter has a user-selectable preset and rollover value
period/rate w/periodic outputs and period/rate w/dynamic outputs
can be used for totalization
The 1771-VHSC module operates in the following modes:
counter mode
encoder X1 mode
encoder X4 mode
period/rate mode
rate measurement frequency mode
continuous/rate mode
The operation of the module in these modes is described below.
The operation of encoder and counter modes is virtually identical.
The only difference between the two modes is in the type of
feedback used.
Use the counter mode if you need the module to read incoming
pulses from a maximum of four encoders (single-ended or
differential), counters, pulse generators, mechanical limit switches,
etc. and return them to the programmable controller as a binary or
BCD number (0-999,999). In counter mode, the module accepts only
one channel feedback.
Use the encoder modes if you need the module to read incoming
quadrature pulses and return them to the programmable controller as
a binary or BCD number (0-999,999). In these modes, the module
accepts two-phase quadrature feedback and counts up or down
depending upon the condition of the phase B input for each counter.
The operation of the module in the encoder/counter modes is as
follows:
Operation in Encoder or
Counter Mode