7–3
Monitoring and Controlling the Loops
Publication
17716.4.5 - January 1997
To change loop settings, at the Loop Monitor screen, click on
Change Settings.
The Change-Settings dialog box appears.
Entering Loop Settings
Enter loop settings values within the stated ranges. In each case
where a decimal point is shown, if you want to enter a digit to the
right of the decimal point, you must type in the decimal point. The
decimal point is not inferred.
In this field: Enter this value:
Loop Mode Control, Monitor, or Off
Alarm Enable Enable or Disable
Run/Standby Run or Standby
Auto / Manual Auto or Manual
SP Ramp Enable enable or disable
SP Ramp Hold Ramp or Hold
When Hold is selected during set point ramping, the ramp will
be stopped and the set point will hold at its current value.
When Ramp is selected, the ramp will continue normally. After
changing the selection, you must perform a download for your
change to take effect. If Setpoint Ramping is disabled, this
setting has no effect.
Note: This feature is only supported in Module Firmware
Version 3.3. and later.
Run Setpoint
0.0 thru 3276.7°
Standby Setpoint
0.0 thru 3276.7°
Manual Output Value -100.00 thru +100.00
Changing Loop Settings