Manual
Locationg Errors
Appendix B
B-2
The second word for each loop indicates dynamic-block and auto-tuning
errors for that loop.
Display of integer value in word 4,
7
,
10
,
13
,
16
,
19
,
22, or 25 of the
status block
A nonzero value in
these two digits
indicate an error in the
autotuning process
A nonzero value in
these two digits
indicate an error in the
dynamic block
Example: If a value 6724 is diplayed, the 67 in the upper
pair of digits would indicate an error in autotuning and the 24
in the leastsignificant pair of digits would indicate an error in
the dynamic block
If This Word of
Status Block:
Contains This
Value:
The Error is:
4 (loop 1)
7(loop2)
xx00 No error detected in dynamic block.
7 (loop 2)
10 (loop 3)
13 (loop 4)
16 (loop 5)
19 (loop 6)
22 (loop 7)
25 (loop 8)
xx01
thru
xx34
A word in the dynamic block has an outofrange value
or incompatible bit selection. Locate the specific word
by the value in the 2 leastsignificant decimal digits of
the status word. (value = word)
•Example: If the value in word 13 is xx17, word 17
(loop4 manual output value) of the dynamic block
has an outofrange value,
00xx No error in autotuning the loop.
65xx Autotuning terminated because of thermal runaway.
66xx Autotuning terminated because the change in PV
(since initial PV temperature) has exceeded 200
.
67xx
Autotuning terminated because PV is within 50
of
setpoint.