Manual
Monitoring Status Data
Chapter 7
7-22
Word DescriptionBits
62
6 Loop7 Low Deviation Alarm (set in word 19 of the configuration block)
•0 = Loop7 PV input is above the low deviation alarm value.
•1 = Loop7 PV input is at or below the low deviation alarm value.
7 Loop8 Low Deviation Alarm (set in word 19 of the configuration block)
•0 = Loop8 PV input is above the low deviation alarm value.
•1 = Loop8 PV input is at or below the low deviation alarm value.
8 Loop1 High Deviation Alarm (set in word 20 of the configuration block)
•0 = Loop1 PV input is below the high deviation alarm value.
•1 = Loop1 PV input is at or above the high deviation alarm value.
9 Loop2 High Deviation Alarm (set in word 20 of the configuration block)
•0 = Loop2 PV input is below the high deviation alarm value.
•1 = Loop2 PV input is at or above the high deviation alarm value.
10 Loop3 High Deviation Alarm (set in word 20 of the configuration block)
•0 = Loop3 PV input is below the high deviation alarm value.
•1 = Loop3 PV input is at or above the high deviation alarm value.
11 Loop4 High Deviation Alarm (set in word 20 of the configuration block)
•0 = Loop4 PV input is below the high deviation alarm value.
•1 = Loop4 PV input is at or above the high deviation alarm value.
12 Loop5 High Deviation Alarm (set in word 20 of the configuration block)
•0 = Loop5 PV input is below the high deviation alarm value.
•1 = Loop5 PV input is at or above the high deviation alarm value.
13 Loop6 High Deviation Alarm (set in word 20 of the configuration block)
•0 = Loop6 PV input is below the high deviation alarm value.
•1 = Loop6 PV input is at or above the high deviation alarm value.
14 Loop7 High Deviation Alarm (set in word 20 of the configuration block)
•0 = Loop7 PV input is below the high deviation alarm value.
•1 = Loop7 PV input is at or above the high deviation alarm value.
15 Loop8 High Deviation Alarm (set in word 20 of the configuration block)
•0 = Loop8 PV input is below the high deviation alarm value.
•1 = Loop8 PV input is at or above the high deviation alarm value.