Monitoring Status Data
Chapter 7
7-20
Word DescriptionBits
61
8 Loop1 Input High Temperature Alarm (set in word 18 of the configuration block)
•0 = Loop1 PV input is below the high temperature alarm value.
•1 = Loop1 PV input is at or above the high temperature alarm value.
9 Loop2 Input High Temperature Alarm (set in word 18 of the configuration block)
•0 = Loop2 PV input is below the high temperature alarm value.
•1 = Loop2 PV input is at or above the high temperature alarm value.
10 Loop3 Input High Temperature Alarm (set in word 18 of the configuration block)
•0 = Loop3 PV input is below the high temperature alarm value.
•1 = Loop3 PV input is at or above the high temperature alarm value.
11 Loop4 Input High Temperature Alarm (set in word 18 of the configuration block)
•0 = Loop4 PV input is below the high temperature alarm value.
•1 = Loop4 PV input is at or above the high temperature alarm value.
12 Loop5 Input High Temperature Alarm (set in word 18 of the configuration block)
•0 = Loop4 PV input is below the high temperature alarm value.
•1 = Loop4 PV input is at or above the high temperature alarm value.
13 Loop6 Input High Temperature Alarm (set in word 18 of the configuration block)
•0 = Loop5 PV input is below the high temperature alarm value.
•1 = Loop5 PV input is at or above the high temperature alarm value.
14 Loop7 Input High Temperature Alarm (set in word 18 of the configuration block)
•0 = Loop6 PV input is below the high temperature alarm value.
•1 = Loop6 PV input is at or above the high temperature alarm value.
15 Loop8 Input High Temperature Alarm (set in word 18 of the configuration block)
•0 = Loop7 PV input is below the high temperature alarm value.
•1 = Loop7 PV input is at or above the high temperature alarm value.