Chapter 7
Monitoring Status Data
7-19
Word DescriptionBits
57 0-15
Loop7 PID Error Value (-3276.7
thru +3276.7
)
58 0-15
Loop8 PID Error Value (-3276.7
thru +3276.7
)
59 0-15
ColdJunctionCompensation Temperature (0
C thru +70.0
C)
60
0
ColdJunctionCompensation Temperature Low Alarm (0
C thru +70
C)
•0 = Coldjunctioncompensation temperature is 0
C or above.
•1 = Coldjunctioncompensation temperature is below 0
C.
1
ColdJunctionCompensation Temperature High Alarm (0
C thru +70
C)
•0 = Coldjunctioncompensation temperature is 70
C or below.
•1 = Coldjunctioncompensation temperature is above 70
C.
2 AutoTuning in Progress (controlled by bit 1 of word 34 of the dynamic block)
•0 = Autotuning not in progress
•1 = Autotuning in progress
3-15 Reserved.
61
0 Loop1 Input Low Temperature Alarm (set in word 17 of the configuration block)
•0 = Loop1 PV input is above the low temperature alarm value.
•1 = Loop1 PV input is at or below the low temperature alarm value.
1 Loop2 Input Low Temperature Alarm (set in word 17 of the configuration block)
•0 = Loop2 PV input is above the low temperature alarm value.
•1 = Loop2 PV input is at or below the low temperature alarm value.
2 Loop3 Input Low Temperature Alarm (set in word 17 of the configuration block)
•0 = Loop3 PV input is above the low temperature alarm value.
•1 = Loop3 PV input is at or below the low temperature alarm value.
3 Loop4 Input Low Temperature Alarm (set in word 17 of the configuration block)
•0 = Loop4 PV input is above the low temperature alarm value.
•1 = Loop4 PV input is at or below the low temperature alarm value.
4 Loop5 Input Low Temperature Alarm (set in word 17 of the configuration block)
•0 = Loop5 PV input is above the low temperature alarm value.
•1 = Loop5 PV input is at or below the low temperature alarm value.
5 Loop6 Input Low Temperature Alarm (set in word 17 of the configuration block)
•0 = Loop6 PV input is above the low temperature alarm value.
•1 = Loop6 PV input is at or below the low temperature alarm value.
6 Loop7 Input Low Temperature Alarm (set in word 17 of the configuration block)
•0 = Loop7 PV input is above the low temperature alarm value.
•1 = Loop7 PV input is at or below the low temperature alarm value.
7 Loop8 Input Low Temperature Alarm (set in word 17 of the configuration block)
•0 = Loop8 PV input is above the low temperature alarm value.
•1 = Loop8 PV input is at or below the low temperature alarm value.