Manual
Monitoring Status Data
Chapter 7
7-12
Word DescriptionBits
17
0 Loop6 Enable
•0 = Loop 6 disabled.
•1 = Loop 6 enabled.
1 Loop6 Auto/Manual Mode Select (controlled by bit 1 of word 22 of the dynamic block)
•0 = Loop 6 is in the manual mode the manual output value (from word 25, dynamic block) is used as the CV value.
•1 = Loop 6 is in the automatic mode the PID algorithm generates the CV value.
2 Loop6 Open Circuit
•0 = Loop6 thermocouple circuit is closed (connection OK).
•1 = .Loop6 thermocouple circuit is open (connection broken).
3 Loop6 Parameters valid
•0 = Power has been interrupted since valid parameters for loop 6 have been blocktransferred.
•1 = Valid parameters for loop 6 have been blocktransferred since last loss of power .
4 Loop6 Calibration Fault
•0 = Loop1 calibration is OK.
•1 = Loop1 cannot operate with as calibrated.
5 Loop6 SetPoint Select (controlled by bit 2 of word 22 of the dynamic block)
•0 = Select the standbytemperature setpoint value from word 23 of the dynamic block.
•1 = Select the runtemperature setpoint value from word 24 of the dynamic block.
6 Loop6 Parameter Value Error
•0 = Loop6 parameter values OK.
•1 = Loop6 parameter value error.
7 Loop6 AutoTuning Complete
•0 = Loop6 autotuning is not complete.
•1 = Loop6 autotuning is complete.
8 Reserved.
9 Reserved.
10 Loop6 Thermal Runaway (set in words 22 and 23 of the configuration block)
•0 = Loop6 is operating within thermal runaway limit..
•1 = Loop6 has exceeded the thermal runaway limit. and the CV value has been forced..
11 Loop6 High CV Limit (set in word 7 of the configuration block)
•0 = Loop6 CV value is below the high CV limit.
•1 = Loop6 CV value is at the high CV limit.
12 Loop6 Low CV Limit (set in word 8 of the configuration block)
•0 = Loop6 CV value is above the low CV limit.
•1 = Loop6 CV value is at the low CV limit.