Monitoring Status Data
Chapter 7
7-10
Word DescriptionBits
14
0 Loop5 Enable
0 = Loop 5 disabled.
1 = Loop 5 enabled.
1 Loop5 Auto/Manual Mode Select  (controlled by bit 1 of word 18 of the dynamic block)
0 = Loop 5 is in the manual mode  the manual output value (from word 21, dynamic block) is used as the CV value.
1 = Loop 5 is in the automatic mode  the PID algorithm generates the CV value.
2 Loop5 Open Circuit
0 = Loop5 thermocouple circuit is closed (connection OK).
1 = .Loop5 thermocouple circuit is open (connection broken).
3 Loop5 Parameters valid
0 = Power has been interrupted since valid parameters for loop 5 have been blocktransferred.
1 = Valid parameters for loop 5 have been blocktransferred since last loss of power .
4 Loop5 Calibration Fault
0 = Loop5 calibration is OK.
1 = Loop5 cannot operate with as calibrated.
5 Loop5 SetPoint Select  (controlled by bit 2 of word 18 of the dynamic block)
0 = Select the standbytemperature setpoint value from word 19 of the dynamic block.
1 = Select the runtemperature setpoint value from word 20 of the dynamic block.
6 Loop5 Parameter Value Error
0 = Loop5 parameter values OK.
1 = Loop5 parameter value error.
7 Loop5 AutoTuning Complete
0 = Loop5 autotuning is not complete.
1 = Loop5 autotuning is complete.
8 Reserved.
9 Reserved.
10 Loop5 Thermal Runaway  (set in words 22 and 23 of the configuration block)
0 = Loop5 is operating within thermal runaway limit..
1 = Loop5 has exceeded the thermal runaway limit. and the CV value has been forced..
11 Loop5 High CV Limit  (set in word 7 of the configuration block)
0 = Loop5 CV value is below the high CV limit.
1 = Loop5 CV value is at the high CV limit.
12 Loop5 Low CV Limit  (set in word 8 of the configuration block)
0 = Loop5 CV value is above the low CV limit.
1 = Loop5 CV value is at the low CV limit.