Operating the Module
Chapter 6
6-6
Word DescriptionBits
24 0-15
Loop6 Run Temperature Setpoint Value Used when bit 2 of word 22 is on (0 thru 999.9
).
25 0-15 Loop6 Manual Output Value (CV) Used when bit 1 of word 22 is off (-100.00 thru +100.00).
26
0 Loop7 Enable
•0 = Loop 7 disabled.
•1 = Loop 7 enabled if PID control mode selected (bits 7-8, word 2, config block).
1 Loop7 Auto/Manual Mode Select
•0 = Loop 7 is in the manual mode the manual output value (from word 29) is used as the CV value.
•1 = Loop 7 is in the automatic mode the PID algorithm generates the CV value.
2 Loop7 SetPoint Select
•0 = Select the standbytemperature setpoint value from word 27.
•1 = Select the runtemperature setpoint value from word 28.
3 Loop7 AutoTuning Enable
•0 = Disable autotuning.
•1 = Enable autotuning autotuning can be invoked by an offtoon transition of bit 1 of word 34.
4 Always = 0.
5 Loop7 PID Integral Term Reset Enable
•0 = Accumulate PID integral term.
•1 = Reset the PID integral term on the 0to1 transition, and then allow accumulation until the next 0to1 transition.
6-15 Always = 0.
27 0-15
Loop7 Standby Temperature Setpoint Value Used when bit 2 of word 26 is off (0 thru 999.9
).
28 0-15
Loop7 Run Temperature Setpoint Value Used when bit 2 of word 26 is on (0 thru 999.9
).
29 0-15 Loop7 Manual Output Value (CV) Used when bit 1 of word 26 is off (-100.00 thru +100.00).