Installing the Module
Chapter 2
2-8
The remote termination panel wiring terminals are shown in Figure 2.5.
Figure 2.5
Connecting
W
ire to the Remote T
ermination Panel
Remote
Termination
Panel (RTP)
channel 2
I = input
O = not used
Field Wiring
S = shield
R = return
channel 1
To connect thermocouple wiring (22-12 AWG) to the remote termination
panel:
1. Strip 9 mm (3/8 inch) of insulation from the wire.
2. Insert the wire into the open connector slot.
3. Tighten the screw to clamp the wire.