4–3Programming Error Codes
Publication
1771-6.5.126 – March 1998
MCC – Module Configuration Command Block ID = 1
Error Code
Description MCC ID = 1
0211 MCC11 is out of range. MCC11 must be within:
00000
MCC11 01000 (0 to 10 V dc sensor)
00100
MCC11 00500 (1 to 5 V dc sensor)
00400
MCC11 02000 (4 to 20 mA dc sensor)
0212 MCC12 is out of range. MCC12 must be within:
00000
MCC12 01000 (0 to 10 V dc sensor)
00100
MCC12 00500 (1 to 5 V dc sensor)
00400 MCC12 02000 (4 to 20 mA dc sensor)
0215
MCC15 is out of range. Valid range is 00000 MCC15 00099
0216
MCC16 is out of range. Valid range is 00000 MCC16 00099
0219 MCC19 is out of range. MCC19 must be within:
00000
MCC19 01000 (0 to 10 V dc sensor)
00100
MCC19 00500 (1 to 5 V dc sensor)
00400 MCC19 02000 (4 to 20 mA dc sensor)
0220 MCC20 is out of range. MCC20 must be within:
00000
MCC20 01000 (0 to 10 V dc sensor)
00100 MCC20 00500 (1 to 5 V dc sensor)
00400 MCC20 02000 (4 to 20 mA dc sensor)
0222
MCC22 is out of range. Valid range is 00000 MCC22 00099
0225 MCC25 is out of range. MCC25 must be within:
00000
MCC25 01000 (0 to 10 V dc sensor)
00100 MCC25 00500 (1 to 5 V dc sensor)
00400
MCC25 02000 (4 to 20 mA dc sensor)
0226 MCC26 is out of range. MCC26 must be within:
00000
MCC26 01000 (0 to 10 V dc sensor)
00100
MCC26 00500 (1 to 5 V dc sensor)
00400 MCC26 02000 (4 to 20 mA dc sensor)
0229
MCC29 is out of range. Valid range is 00000 MCC29 00099
0230
MCC30 is out of range. Valid range is 00000 MCC30 00099
0233 MCC33 is out of range. MCC33 must be within:
00000
MCC33 01000 (0 to 10 V dc sensor)
00100
MCC33 00500 (1 to 5 V dc sensor)
00400 MCC33 02000 (4 to 20 mA dc sensor)
0234 MCC34 is out of range. MCC34 must be within:
00000
MCC34 01000 (0 to 10 V dc sensor)
00100 MCC34 00500 (1 to 5 V dc sensor)
00400
MCC34 02000 (4 to 20 mA dc sensor)
0236
MCC36 is out of range. Valid range is 00000 MCC36 00099
0239 MCC39 is out of range. MCC39 must be within:
00000
MCC39 01000 (0 to 10 V dc sensor)
00100 MCC39 00500 (1 to 5 V dc sensor)
00400
MCC39 02000 (4 to 20 mA dc sensor)
0240 MCC40 is out of range. MCC40 must be within:
00000
MCC40 01000 (0 to 10 V dc sensor)
00100
MCC40 00500 (1 to 5 V dc sensor)
00400
MCC40 02000 (4 to 20 mA dc sensor)
0243
MCC43 is out of range. Valid range is 00000 MCC43 00099
0244
MCC44 is out of range. Valid range is 00000 MCC44 00099
0247 MCC47 is out of range. MCC47 must be within:
00000
MCC47 01000 (0 to 10 V dc sensor)
00100 MCC47 00500 (1 to 5 V dc sensor)
00400
MCC47 02000 (4 to 20 mA dc sensor)