User Manual
Table Of Contents
- 1771-6.5.88, Plastic Molding Module Reference Manual
- Summary of Changes
- Table of Contents
- Preface
- 1 - Abbreviated Command and Status Blocks
- Chapter Contents
- CLC - Clamp and Eject ERC Values Block
- CPC - Clamp Close Profile Block
- DYC - Dynamic Command Block
- EAC - Ejector Advance Configuration Block
- EPC - Ejector Profile Block
- ERC - Ejector Retract Configuration Block
- FCC - First Clamp Close Configuration Block
- FOC - First Clamp Open Configuration Block
- HDC - Hold Configuration Block
- HPC - Pack/Hold Profile Block
- INC - Injection Configuration Block
- IPC - Injection Profile Block
- JGC - Jog Configuration Block
- LPC - Clamp Low Pressure Close Configuration Block
- MCC - Module Configuration Command Block
- OPC - Clamp Open Profile Block
- OSC - Clamp Open Slow Configuration Block
- PKC - Pack Configuration Block
- PLC - Plastication Configuration Block
- PPC - Plastication Profile Block
- PRC - Pre-decompression Configuration Block
- PSC - Post- decompression Configuration Block
- PTC - Process Trace Configuration Block
- RLC - Inject ERC Values Block
- SCC - Second Clamp Close Configuration Block
- SOC - Second Clamp Open Configuration Block
- TCC - Third Clamp Close Configuration Block
- TOC - Third Clamp Open Configuration Block
- CLS - Clamp and Eject ERC Values Status Block
- CPS - Clamp Close Profiles Status Block
- EPS - Ejector Profile Status Block
- HPS - Pack/Hold Profile Status Block
- IPS - Injection Profile Status Block
- OPS - Clamp Open Profiles Status Block
- PPS - Plastication Profile Status Block
- PTS - Process Trace Status Block
- RLS - Inject ERC Values Status Block
- SYS - System Status Block
- 2 - Command Word/Bit Descriptions
- Alphabetical List of Command Blocks and Block ID Codes
- List of Data Words
- Engineering Units
- Data Blocks Require I/O Configuration
- Data Blocks for System Control
- Data Blocks for Controlling Ram (Screw) Position
- Data Blocks for Controlling Clamp Position
- Data Blocks for Controlling Ejector Position
- Sensors Required
- CLC CLC - Clamp and Eject ERC Values Block
- CPC - Clamp Close Profile Block
- DYC DYC - Dynamic Command Block
- EAC - Ejector Advance Configuration Block
- EPC - Ejector Profile Block
- ERC - Ejector Retract Configuration Block
- FCC - First Clamp Close Configuration Block
- FOC - First Clamp Open Configuration Block
- HDC - Hold Configuration Block
- HPC - Pack/Hold Profile Block
- INC - Injection Configuration Block
- IPC - Injection Profile Block
- JGC - Jog Configuration Block
- LPC - Clamp Low Pressure Close Configuration Block
- MCC - Module Configuration Command Block
- OPC - Clamp Open Profile Block
- OSC - Clamp Open Slow Configuration Block
- PKC - Pack Configuration Block
- PLC Plastication Configuration Command Block (PLC)
- PPC - Plastication Profile Block
- PRC - Pre-decompression Configuration Block
- PSC - Post-decompression Configuration Block
- PTC - Process Trace Configuration Block
- RLC - Inject ERC Values Block
- SCC - Second Clamp Close Configuration Block
- SOC - Second Clamp Open Configuration Block
- TCC - Third Clamp Close Configuration Block
- TOC - Third Clamp Open Configuration Block
- 3 - Word/Bit Descriptions
- List of Status Blocks and Block ID Codes
- List of Data Words
- Data Blocks Require I/O Configuration
- Engineering Units
- Status Block for Reporting System Status
- Status Blocks for Reporting Ram (Screw) Position
- Status Blocks for Reporting Clamp Position
- Status Blocks for Reporting Ejector Position
- CLS - Clamp and Eject ERC Values Status Block
- CPS - Clamp Close Profiles Status Block
- EPS - Ejector Profile Status Block
- HPS - Pack/Hold Profile Status Block
- IPS ú Injection Profile Status Block
- OPS - Clamp Open Profiles Status Block
- PPS - Plastication Profile Status Block
- PTS - Process Trace Status Block
- RLS - Inject ERC Values Status Block
- SYS - System Status Block
- 4 - Programming Error Codes
- 5 - Module Specifications
- 6 - Calibration Instructions
- A - Single transfer for Reporting Ejector Status
- Back cover

4–19Programming Error Codes
Publication
1771-6.5.88 – July 1997
Error Code
Description
ID = 9
0212
IPC12 is out of range. Valid range is 00000
≤
IPC12
≤
09999
0213 IPC13 is out of range.
When IPC03-B01 = 0, IPC13 must be within 00000
≤
IPC13
≤
09999
0216
IPC16 is out of range. Valid range is 00000
≤
IPC16
≤
09999
0217 IPC17 is out of range.
When IPC03-B01 = 0, IPC17 must be within 00000
≤
IPC17
≤
09999
0220
IPC20 is out of range. Valid range is 00000
≤
IPC20
≤
09999
0221 IPC21 is out of range.
When IPC03-B01 = 0, IPC21 must be within 00000
≤
IPC21
≤
09999
0224
IPC24 is out of range. Valid range is 00000
≤
IPC24
≤
09999
0225 IPC25 is out of range.
When IPC03-B01 = 0, IPC25 must be within 00000
≤
IPC25
≤
09999
0228
IPC28 is out of range. Valid range is 00000
≤
IPC28
≤
09999
0229 IPC29 is out of range.
When IPC03-B01 = 0, IPC29 must be within 00000
≤
IPC29
≤
09999
0232
IPC32 is out of range. Valid range is 00000
≤
IPC32
≤
09999
0233 IPC33 is out of range.
When IPC03-B01 = 0, IPC33 must be within 00000
≤
IPC33
≤
09999
0236
IPC36 is out of range. Valid range is 00000
≤
IPC36
≤
09999
0237 IPC37 is out of range.
When IPC03-B01 = 0, IPC37 must be within 00000
≤
IPC37
≤
09999
0240
IPC40 is out of range. Valid range is 00000
≤
IPC40
≤
09999
0241 IPC41 is out of range.
When IPC03-B01 = 0, IPC41 must be within 00000
≤
IPC41
≤
09999
0244
IPC44 is out of range. Valid range is 00000
≤
IPC44
≤
09999
0245 IPC45 is out of range.
When IPC03-B01 = 0, IPC45 must be within 00000
≤
IPC45
≤
09999
0248
IPC48 is out of range. Valid range is 00000
≤
IPC48
≤
09999
0249 IPC49 is out of range.
When IPC03-B01 = 0, IPC49 must be within 00000
≤
IPC49
≤
09999
0251 IPC51 is out of range.
When IPC03-B01 = 0, IPC51 must be within 00000
≤
IPC51
≤
09999
0259
IPC59 is out of range. Valid range is 00000
≤
IPC59
≤
00099
0260
IPC60 is out of range. Valid range is 00000
≤
IPC60
≤
09999
0409 IPC09 is out of range.
When IPC03-B14 = 1, a non-zero entry for IPC09 must be within INC45
≤
IPC09
≤
INC46
0410 IPC10 is out of range.
If non-zero, IPC10 must be within INC41
≤
IPC10
≤
INC42
0411 IPC11 is out of range.
if: then:
MCC13 and MCC14 IPC11 must be within 00000
≤
IPC11
≤
MCC14 – MCC13
are both non-zero
MCC13 is non-zero and IPC11 must be within 00000
≤
IPC11
≤
MCC10 – MCC13.
MCC14 is zero
MCC13 is zero and IPC11 must be within 00000
≤
IPC11
≤
MCC14 – MCC09.
MCC14 is non-zero
MCC13 and MCC14 IPC11 must be within 00000
≤
IPC11
≤
MCC10 – MCC09
are both zero
0413 IPC13 is out of range.
When IPC03-B14 = 1, a non-zero IPC13 must be within INC45
≤
IPC13
≤
INC46
0414 IPC14 is out of range.
If non-zero, IPC14 must be within INC41
≤
IPC14
≤
INC42