User guide

Configure the QDC Module's I/O
Chapter 3
3-4
To determine initial sensor configuration values, refer to Table 3.A, and
specifications that accompanied your sensors, valves, and cylinders. Write
down applicable values on Worksheet 3-D.
Important: You must enter floating-point numbers and percentages as
integers, so we recommend that you write them in Worksheet 3-D in the
following format: Use an assumed decimal point position that depends on
the range value. For example:
If the Range is: And You Want to
Enter this Value:
Use this
Format:
0  099.99% 75% 07500
0  99.99 inch 7.32 inch 00732
0  0999.9 mm 432.6 mm 4326
4.00  020.00 mA 16 mA 01600
0  010.00V dc 5.6V dc 00560
0  009.99 sec 0.47 sec 00047
0  09999 psi 321 psi 00321
0  0999.9 Bar 222 Bar 2220
Table 3.A
Determine
Initial Sensorconfiguration V
alues for W
orksheet 3D
Category: If your: Then Use a Value Equal to:
Minimum Position (Lines 1, 9, and 13) N/A zero
Maximum Position (Lines 2, 10, and 14) Actuator is fully extended full travel of the sensor
Analog Signal @ Min Position sensor is forwardacting low end of your selected range
(Lines 3, 11, and 15) sensor is reverseacting high end of your selected range
Analog Signal @ Max Position sensor is forwardacting high end of your selected range
(Lines 4, 12, and 16) sensor is reverseacting low end of your selected range
Minimum System Pressure (Line 5) N/A min range value specified by manufacturer
Maximum System Pressure (Lines 6) N/A max range value specified by manufacturer
Analog Signal @ Min System Pressure sensors are forwardacting low end of your selected range
(Line 7) sensors are reverseacting high end of your selected range
Analog Signal @ Max System Pressure sensors are forwardacting high end of your selected range
(Line 8) sensors are reverseacting low end of your selected range
Determine
Initial
Sensorconfiguration Values