Chapter 5
5-2
Worksheet 5-A outlines all values necessary to successfully configure your
QDC module for clamp and ejector jogs. Enter initial values to allow
minimal actuator motion during jogs. Later in this chapter, we gradually
increase these values until we reach the desired jog values.
At this time, also enter in jog high pressure setpoints in Worksheet 5-A.
The QDC module sets an alarm any time clamp or ejector pressure equals
or exceeds the respective value during clamp and ejector jogs. A zero
entry inhibits alarm actuation.
Important: High clamp pressure and high ejector pressure alarms (set in
chapter 3), are also active during jog functions.
Worksheet 5A
Initial
Clamp and Eject Jog Configuration V
alues
Control Block
Word
ProSet 600 Addr. Value Description Units
Clamp, Forward Jog
JGC33 N41:89 Set Output Values Output #1 % Signal Output
2
JGC34 N41:90 Output #2 % Signal Output
2
JGC35 N41:91 Output #3 % Signal Output
2
JGC36 N41:92 Output #4 % Signal Output
2
Clamp, Reverse Jog
JGC41 N41:97 Set Output Values Output #1 % Signal Output
2
JGC42 N41:98 Output #2 % Signal Output
2
JGC43 N41:99 Output #3 % Signal Output
2
JGC44 N41:100 Output #4 % Signal Output
2
Ejector, Advance Jog
JGC49 N41:105 Set Output Values Output #1 % Signal Output
2
JGC50 N41:106 Output #2 % Signal Output
2
JGC51 N41:107 Output #3 % Signal Output
2
JGC52 N41:108 Output #4 % Signal Output
2
Ejector, Retract Jog
JGC57 N41:113 Set Output Values Output #1 % Signal Output
2
JGC58 N41:114 Output #2 % Signal Output
2
JGC59 N41:115 Output #3 % Signal Output
2
JGC60 N41:116 Output #4 % Signal Output
2
Jog Pressure Alarms
JGC07 N41:63 Clamp Jog Pressure Alarm Setpoint Clamp pressure
1
JGC08 N41:64 Ejector Jog Pressure Alarm Setpoint Ejector pressure
1
1
Pressure
2
%
Signal Output
0000 to 9999 PSI
00.00 to 99.99 %
000.0 to 999.9 Bar
Determine Initial Clamp and
Ejector Jog Values